UPS-IND 1300

Uninterruptible Power Supply (UPS)

UPS-IND 1300

Uninterruptible Power Supply (UPS)
10 ~ 30 kVA
Capacity
+/-1%
Voltage regulation
2 Year Warranty

Complete On Line Double Conversion UPS offers protection in complex electrical environments with continuous operation functionality.

  • On Line Double Conversion
  • ECO-IND Mode
  • Smart Ventilation Control
  • DSP Control
  • SNMP Network Card
  • Maintenance Bypass
  • Electronic Bypass

Uninterrupted Power

Icono rayo
On Line Double Conversion
Guarantees clean and stable voltage output despite irregularities on the input.
Icono rayo
Battery Back Up
Standard 5 Minute continuous power back up.
Icono rayo
Smart Ventilation Control
Automatic vent adapts speed in proportion to variations in demand or room temperature.
Icono rayo
ECO-IND Mode
99% efficiency ECO Mode while voltage and frequency are within safe range.
Icono rayo
DSP Control
Digital Signal Processor sustains high precision control and speed for optimal system performance.
Icono rayo
SNMP Network Card
Monitoring equipment alerts, controls and tracks current status of UPS from any off site location.
Icono rayo
Maintenance Bypass
Bypass switch enables safe UPS electrical isolation during maintenance or testing.
Icono rayo
Electronic Bypass
Automatic bypass ensures operational continuity in the event of a failure.
Icono rayo
Automatic Shut Off
Activates when voltage levels reach dangerous levels and reconnects the load only when it is safely within range.

Video

Applications

Buildings
Buildings
Commercial buildings
Commercial buildings
Computer Rooms
Computer Rooms
Data Centers
Data Centers
Hospitals
Hospitals
Machinery
Machinery
Office
Office
Precision Instruments
Precision Instruments
Robotics
Robotics

Technical Specifications

UPS-IND
1346
1350
1353
1358
Capacity (kVA / kW) 10/9 15/13.5 2/18 30/27
Input Voltage (V) 127 / 220 or 120 / 208
Overload Protection Thermomagnetic switch & bypass
Range (Accepted) + 20% at 100% of the load, + 25% at 75% and + 30% at 50%
Phases Star: 3 phase star (4 wires + ground) / Delta: (optional) 3 phases (3 wires + ground)
Frequency 60 ± 10 % (optional 50 ± 10 % )
Power Factor 0.90 when empty > 0.95 at full load
UPS-IND
1346
1350
1353
1358
Overload Protection Thermomagnetic switch on the output
Output Power Factor 0.9
Voltage (Vca) 127 / 220 or 120 / 208
Voltage Regulation Range ± 1% (typical)
Frequency (Hz) 60 ± 0.2% (50 ± 0.2%)
Wave Form THD pure sinusoidal wave ≤ 1% (linear load), ≤ 3% (non-linear load)
Transfer Time (ms) 0.0 (on line)
Connection Type Star (3 phases, 4 wires + ground)
Overload 125% of nominal load for 10 min; 150% for 60 s
UPS-IND
1346
1350
1353
1358
Voltage (Vcd) 192
Battery Type Lead acid (sealed, maintenance free)/ (optional: nickel cadmium)
Battery Backup Time at Full Load (min) 5 – 25 5 – 16 5 – 10 5
Maximum Load Current (A) 22 33 44 67
Battery Bank Internal External
UPS-IND
1346
1350
1353
1358
Audible Noise (dB) < 65, to 1 meter
MTBF (h) 233,000
Operational Temperature (°C) 0~40
Relative Humidity 0 ~ 95% without condensation
Maximum Operating Altitude (mamsl) 2,000 at 100% & 3,000 at 96%
Cabinet Electrostatic baked epoxy coated steel
Dimensions, height x width x depth (mm) 1600 x 500 x 800
Weight (kg) 340 / 532 350 / 542 360 / 552 380 / 572

Request quote

    Power Calculator

    Instantly calculate equipment capacity by filling in the missing information:

    Cerrar
    Whatsapp Whatsapp