Industrial grade protection from dangerous voltage spikes, electrical noise and power line disturbances. Industrial grade design and materials ensure safe and reliable operation for demanding applications.
|
Model SPV-IND
|
50
|
100
|
200
|
400
|
|---|---|---|---|---|
| Nominal Voltage (V) | 110/190, 120/208, 127/220 | |||
| Phases | 3 | |||
| Configuration | Star: 3 Phases, Neutral y Ground | |||
| Protection Voltage (VPR) | 700 V (P-N), 700 V (P-G), 700 V (N-G), 1400 V (P-P) | |||
| >Maximum Current Operation Voltage (MCOV)) | 150 V (P-N, N-G, P-G) | |||
| Type / Recommended application class | Type 1 & Type 2 | |||
| Short Circuit Current Capacity (SCCR) | 200kA | |||
| Nominal Discharge Current (In) | 20kA | |||
| Protection current per phase (kA) | 26 | 40 | 80 | 150 |
| Three-Phase protection current (kA) | 50 | 100 | 200 | 400 |
| Frequency (Hz) | 50/60 | |||
| Energy capacity (J) | 640 | 1280 | 2560 | 4960 |
| Modos de protección | 10 modes P1-N, P1-G, P2-N, P2-G, P3-N, P3-G, N-G, P1-L2, P2-P3, P1-PL3 | |||
| EMI / RFI Filtering | Up to 50 dB at 10 kHz to 100 MHz | |||
|
Model SPV-IND
|
50
|
100
|
200
|
400
|
|---|---|---|---|---|
| Cabinet | NEMA 4, IP 65, 16 caliber galvanized steel with baked epoxy coating in black | |||
| Dimensions, height x width x depth (mm) | 260 x 210 x 90 | |||
| Weight (kgs) | 2.3 | 2.4 | 2.6 | |
| Connection type | 5 flexible cables AWG 10 | 5 flexible cables AWG 8 | ||
|
Model SPV-IND
|
50
|
100
|
200
|
400
|
|---|---|---|---|---|
| Maximum operating altitude (mamsl) | 5,000 | |||
| Operating temperature (°C) | -40 ~ 70 | |||
| LED indicator activation time | < 1 sec | |||
| Relative humidity | from 5% to 95% without condensation | |||
|
Model SPV-IND
|
50
|
100
|
200
|
400
|
|---|---|---|---|---|
| Average efficiency | 100% | |||
| Harmonic distorsion | Does NOT add harmonic distortion to the line | |||
| Anti-ignition system | Thermostable polymer encapsulated varistors & smoke proof sealed metal cabinet | |||
| LED Indicator | Phase failure, phase loss & current between neutral and ground | |||
| Remote monitoring | Dry contact signal (NA, NC, COM)/td> | |||
| Audible indicator | In case of failure or phase loss | |||
| Suggested switch type | 3 poles, 30 A, 250 Vca | |||
| Certifications | Complies with: NOM, UL 1449 3rd Edition; components comply to UL94V-0 | |||
|
100
|
200
|
400
|
530
|
|
|---|---|---|---|---|
| Nominal Voltage (V) | 254 / 440, 266 / 460, 277 / 480 | |||
| Phases | 3 | |||
| Configuration | Star: 3 Phases, Neutral y Ground | |||
| Protection Voltage (VPR) | 1200 V (P-N), 1200 V (P-G), 1200 V (N-G), 2400 V (P-P) | |||
| >Maximum Current Operation Voltage (MCOV)) | 385 V (P-N, N-G, P-G) | |||
| Type / Recommended application class | Type 1 & Type 2 | |||
| Short Circuit Current Capacity (SCCR) | 200kA | |||
| Nominal Discharge Current (In) | 20kA | |||
| Protection current per phase (kA) | 40 | 80 | 150 | 300 |
| Three-Phase protection current (kA) | 100 | 200 | 400 | 530 |
| Frequency (Hz) | 50/60 | |||
| Energy capacity (J) | 1955 | 3910 | 7735 | 10030 |
| Modos de protección | 10 modes P1-N, P1-G, P2-N, P2-G, P3-N, P3-G, N-G, P1-L2, P2-P3, P1-PL3 | |||
| EMI / RFI Filtering | Up to 50 dB at 10 kHz to 100 MHz | |||
|
100
|
200
|
400
|
530
|
|
|---|---|---|---|---|
| Cabinet | NEMA 4, IP 65, 16 caliber galvanized steel with baked epoxy coating in black | |||
| Dimensions, height x width x depth (mm) | 260 x 210 x 90 | |||
| Weight (kgs) | 2.4 | 2.6 | 2.7 | |
| Connection type | 5 flexible cables AWG 10 | 5 flexible cables AWG 8 | ||
|
100
|
200
|
400
|
530
|
|
|---|---|---|---|---|
| Maximum operating altitude (mamsl) | 5,000 | |||
| Operating temperature (°C) | -40 ~ 70 | |||
| LED indicator activation time | < 1 sec | |||
| Relative humidity | from 5% to 95% without condensation | |||
|
100
|
200
|
400
|
530
|
|
|---|---|---|---|---|
| Average efficiency | 100% | |||
| Harmonic distorsion | Does NOT add harmonic distortion to the line | |||
| Anti-ignition system | Thermostable polymer encapsulated varistors & smoke proof sealed metal cabinet | |||
| LED Indicator | Phase failure, phase loss & current between neutral and ground | |||
| Remote monitoring | Dry contact signal (NA, NC, COM)/td> | |||
| Audible indicator | In case of failure or phase loss | |||
| Suggested switch type | 3 poles, 30 A, 600 Vca | |||
| Certifications | Complies with: NOM, UL 1449 3rd Edition; components comply to UL94V-0 | |||
Instantly calculate equipment capacity by filling in the missing information: