New high frecuency HF UPS is the optimum protection for complex electrical networks. Battery back up as well as voltage correction offer continuos protection to connected equipment.
|
UPS-IND HF
|
1206
|
1210
|
|
|---|---|---|---|
| Capacity (kVA / kW) | 6/5.4 (optional 6/6) | 10/9 (optional 10/10) | |
| Input Voltage (V) | 220 | ||
| Overload Protection | Thermomagnetic switch | ||
| Range (Accepted) | – 20%, + 25% (at full load) | ||
| Phases | 2 phases (2 wires + ground) | ||
| Frequency | 40 – 70 (autodetection) | ||
| Power Factor | 0.99 | ||
|
UPS-IND HF
|
1206
|
1210
|
|---|---|---|
| Output Power Factor | 1.0 | |
| Voltage (Vca) | 120 / 208 / 220 / 230 / 240 (adjustable) | |
| Voltage Regulation Range | ± 1% (typical) | |
| Frequency (Hz) | 50 / 60 ± 0.2% (battery mode) | |
| Wave Form | THD pure sinusoidal wave ≤ 1% (linear load), ≤ 3% (non-linear load) | |
| Transfer Time (ms) | 0.0 (on line) | |
| Overload | 105%-125% 10min, 125%-150% 5 min, 150%-200% 5 s, >200% 200 ms. | |
| Load unbalance capability | 100% | |
| Efficiency | 96% | |
|
UPS-IND HF
|
1206
|
1210
|
|---|---|---|
| Voltage (Vcd) | 192 standard (192 -240 adjustable) | |
| Battery Type | 12 volts 7.2 Ah / 12 volts 9 Ah (lead acid, maintenance-free) | |
| Battery Backup Time at Full Load (min) | 3 -5 min. at full load, 9-18 min. at half load | |
| Maximum Load Current (A) | 1.0 – 3.0 (adjustable) | |
| Battery Bank | Internal | |
|
UPS-IND HF
|
1206
|
1210
|
|---|---|---|
| Audible Noise (dB) | < 55, at 1 meter | |
| MTBF (h) | 233,000 | |
| Operational Temperature (°C) | 0 ~ 40 at full load, 50 at 90% of the load | |
| Relative Humidity | 0 ~ 95% without condensation | |
| Maximum Operating Altitude (mamsl) | 2,300 at 100% , 3,100 at 85% | |
| Cabinet | Electrostatic baked epoxy coated steel, NEMA type 1 | |
| Dimensions, height x width x depth (mm) | 720 x 250 x 660 | |
| Weight (kg) | 104 (68 w/o battery) | 128 (88 w/o battery) |
|
UPS-IND HF
|
1206
|
1210
|
|
|---|---|---|---|
| Conversion Type | On-line double conversion (online) | ||
| Rectifier | IGBT Technology | ||
| Inverter | PWM Technology with IGBT conmuted at 19.2 kHz | ||
| Inverter Configuration | H Bridge | ||
| Inverter Type | Pulse width modulated (PWM) | ||
| Battery Status | Real time Online/Discharge information with 3% precision | ||
| Thermal Dissipation (kBTU/h) | 1.8 | 3 | |
| Certifications | CE-IEC 62040 – 1, ISO 9001 : 2015, NOM-001-SCFT-1993 | ||
| Communication Interface | RS-232 + SNMP (EPO Dry contacts, USB, optional) | ||
| Monitor Screen | LCD screen indicates UPS operating status | ||
| Alarm | irregular power supply, low battery voltage & UPS malfunction | ||