Provides 100% operational reliability for any application.
Maximum protection, trusted design.
AMCR
|
5204
|
5206
|
5210
|
5215
|
---|---|---|---|---|
Capacity (kVA / kW) | 4/4 | 6/6 | 10/10 | 15/15 |
Input Voltage (V) | 120/208 | |||
Overload Protection | Thermo-magnetic switch on the output/ fuse (varies by model) | |||
Range (Accepted) | ± 15% | |||
Operational Frequency | 60 ± 10%, does not alter frequency* | |||
Harmonic Distortion | Less than 2 % THD | |||
Power Factor | Does NOT alter, adaptable to load requirement |
* Tolerance available under evaluation of the Engineering department
AMCR
|
5204
|
5206
|
5210
|
5215
|
---|---|---|---|---|
Voltage Regulation Range | ± 5% | |||
Power Supply Impedance | Less than 2% | |||
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) | |||
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) | |||
Reset | Automatic (programmed at factory) | |||
Reset Time | 3 second standard time ** |
** Factory configurable up to 6 kVA on request
AMCR
|
5204
|
5206
|
5210
|
5215
|
---|---|---|---|---|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use | |||
Input / Output Connectors | Terminal block (clamps) (G, N, L1, L2)** | |||
Transformers | Electrolytic copper magnetic wire and silicon steel sheet | |||
Cooling & Ventilation | Natural convection | |||
Cabinet | Galvanized steel sheet metal | |||
Paint Finish | Primer and electrostatic epoxy powder coating | |||
Maximum Altitude Of Operation (mamsl) | 3,000 | |||
Operational Temperature (°C) | 0 ~ 40 | |||
Relative Humidity | 0 ~ 95% without condensation | |||
Dimensions, height x width x depth (mm) | 460 x 270 x 450 | |||
Weight (kg) | 18 | 21 | 28 | 35 |
** Factory configurable up to 6 kVA on request
AMCR
|
5204
|
5206
|
5210
|
5215
|
---|---|---|---|---|
High Frequency Noise Protection | PI Filter | |||
Control Technology | Microcontroller | |||
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) | |||
Measurement Parameters | Voltage, current, power and kWh | |||
Electronic Commutation | TRIACs |
AMCR
|
5204
|
5206
|
5210
|
5215
|
---|---|---|---|---|
Transformer | Type H | |||
Spike Suppressor | Varistors on the output | |||
Efficiency | 98% minimum | |||
Overload Capacity | Up to 400% in intermittent startups |